FlashKeepers

HVAC/EPA 608 · EPA 608 Type III

EPA 608: Type III Low-Pressure Appliances

Rules and procedures for servicing low-pressure chillers, tested on the Type III certification.

29 cards · basic cards · AI-written, checked twice. Edit anything.

Study this set free Look inside first Get FlashKeepers for iPhone
What is a low-pressure appliance under EPA 608 Type III?
An appliance designed to operate with refrigerant pressures normally below 10 psig, typically a low-pressure chiller.
What is the most common refrigerant used in Type III low-pressure chillers?
CFC-11 (trichlorofluoromethane), historically the standard for low-pressure chillers.
What is the purpose of a liquid indicator glass in a low-pressure system?
To visually observe refrigerant level and detect moisture by color changes.
What is the function of a purge unit in a low-pressure chiller?
To remove non-condensable gases and moisture that accumulate in the system over time.
How must refrigerant be recovered from a low-pressure appliance?
By using a certified recovery system with adequate storage capacity, never vented to atmosphere.
What is the maximum moisture content allowable in a low-pressure chiller system?
15 parts per million (ppm) by weight.
What pressure relief device protection is required for low-pressure chillers?
At least one pressure relief valve set to relieve at the maximum allowable working pressure.
What acid test is required after opening a Type III system?
An acid number test (ASTM D664) to detect acid formation, max 0.1 mg KOH/g.
How should lines be protected after opening a Type III system?
All open lines must be capped or plugged immediately to prevent moisture and air entry.
What leak detection method is prohibited on low-pressure chillers?
Pressurizing the system with air or oxygen to search for leaks.
What type of expansion device is used in low-pressure chillers?
Thermostatic expansion valve (TXV) or capillary tube, not orifice plates.
How is the compressor motor cooled in a low-pressure chiller?
By direct contact with the low-pressure refrigerant vapor, which provides motor cooling.
What is the cylinder color code for CFC-11 refrigerant?
Green (or white for recovery cylinders containing CFC-11).
What EPA violation carries the highest penalty for improper venting?
Venting CFC or HCFC refrigerant intentionally; penalties exceed $40,000 per violation.
What must be documented on a service record for Type III systems?
Refrigerant added, amount recovered, compressor status, oil condition, and acid test results.

14 more cards in the app